Away from the Roar of Diesel: A Case Record of Solar-Storage System for a Courtyard Along the Street in Ghana
At 6:40 in the evening, the diesel engine in the yard fell silent.
It was not shut down; someone flipped the switch. A moment of quiet followed, then the compressor of the freezer hummed to life. The ceiling fan spun slowly for a few rotations before picking up speed, and the lamp on the wall lit up, casting a patch of light over the plastic chair by the doorway. Someone in the kitchen poked their head out, then ducked back as oil sizzled in the pan.
This courtyard sits in a riverside township in the Eastern Region of Ghana. The front section serves as a shop: an upright chest freezer for fish, a display chiller for drinks and yoghurt, and shelves lined against the wall stocked with batteries, laundry soap and biscuits. The rear section is the home: three rooms, a kitchen, and a concrete wash basin. At the centre of the yard stands a well. When the pump starts, the water runs muddy at first and clears after a while.

Before this system was installed, the two hours around dusk were the hardest part of the day. The diesel engine ran from six to eleven at night, clattering like metal being struck repeatedly. Smoke drifted up past the windowsills, and people had to raise their voices to talk inside. Two men were needed to lift the oil drum for refuelling. Noise was not the main worry — the risk was unplanned shutdowns. Once the frozen fish thawed, they could only be eaten by the family the next day.
The diesel unit still sits in the corner with oil stored on hand, yet it has been relegated to backup duty. The real work is handled by ten solar panels on the roof, an inverter mounted on the wall, and an energy storage cabinet on the ground.

01 How much power does this courtyard consume daily
Designers often make a common mistake: starting with equipment parameters and then calculating what loads they can support. We take the opposite approach: map out the full daily routine first, then verify whether the system capacity is adequate.
Before sunrise, the well pump kicks in. Rated at 1.1 kW, it runs for forty minutes twice a day. All domestic water use — drinking, washing, yard cleaning — relies on these eighty minutes of operation. It can run at any time, though ideally not during peak cooking hours to avoid power conflicts.
Late morning through the afternoon is the quietest yet hottest period for the shop. Three ceiling fans, 75 W each, run almost nonstop from 9 a.m. until 10 p.m. A 200-litre household fridge consumes roughly 1.2 kWh per day. The two commercial refrigerators are far more demanding. With frequent door openings and ambient temperatures around 35°C while maintaining sub-zero internal temperatures, their compressors cycle frequently, consuming about 4.5 kWh combined daily.
Cooking at noon with an induction cooker and rice cooker takes around one hour and uses 2 kWh. The washing machine runs every other day, averaging 0.5 kWh daily. Small loads including mobile phones, router and signage lighting add another 0.3 kWh.
Peak demand arrives at dusk. Twelve 9 W LED lights draw 108 W from 6 p.m. to 11 p.m., consuming 0.5 kWh. A television and set-top box run for six hours, using 0.7 kWh. The 1.5 HP variable-frequency air conditioner runs for six hours overnight, blowing directly over the bed, with its compressor operating at approximately 70% load for a total consumption of 4.5 kWh. When the induction cooker in the kitchen fires up at 1.8 kW, the whole yard’s voltage sags visibly.
Total daily consumption ranges from 18.5 to 19 kWh. We add 2 kWh allowance for occasional extra loads such as power drills and small ice makers, plus a 15% safety margin. No household-cum-shop sticks rigidly to a fixed power schedule. The final design target is set at 24 kWh per day.
Peak load is not about total energy but instantaneous draw. At dusk, the induction cooker draws 1.8 kW and the air conditioner 1.1 kW. If both refrigerators start their compressors simultaneously, the inrush current can reach three to four times the rated value, adding over 4 kW together. Combined with lights, fans, TV and router, the instantaneous load can hit 6 kW. This is not theoretical calculation; it is the typical “all appliances switched on at once” scenario for this type of small commercial residence.
02 Two core units, each with its own role
Wall-mounted unit: 8 kW Inverter

Single-phase, 8 kW rated power. Maximum continuous power 8800 W. Off-grid surge capacity reaches twice the rated power for 10 seconds — this short burst handles the compressor inrush of refrigerators and air conditioners, and is not intended for sustained overload.
AC side: rated output current 36.4 A, maximum 40 A. Mains bypass supports up to 50 A, 220 / 230 V, 50 / 60 Hz, THD < 3%. Standard single-phase L/N/PE wiring.
The DC side is where its core capability lies. Maximum DC input power 10400 W, rated DC voltage 370 V, startup voltage 125 V. MPPT operating window: 150 V – 425 V, full-load MPPT window: 200 V – 425 V. Dual independent MPPT channels. Each channel supports two strings, with per-string maximum input current 26 A and short-circuit current 44 A.
The benefit of dual independent tracking is practical: if one string is shaded by a passing cloud, the other continues operating without performance collapse.
Battery port: 40 V – 60 V, maximum charge/discharge current 190 A. Equipped with an external temperature sensor, supporting three-stage charging plus equalisation and adaptive BMS. The temperature sensor is not decorative: in intense heat, it automatically reduces charging current to protect the battery from harsh 40°C+ ambient conditions in the yard.
Power factor range: 0.8 leading to 0.8 lagging. This parameter rarely matters for current loads, yet it stabilises voltage if water pumps and small motors are added later.
Ground cabinet: 16 kWh Energy Storage Battery

16 kWh nominal capacity: 51.2 V, 314 Ah, 16076 Wh.
Rated charge/discharge current 157 A, peak 200 A. At 200 A × 51.2 V, the discharge capability exceeds 10 kW, higher than the inverter’s 8 kW rating. That means the inverter, not the battery, defines the system power limit.
Charging voltage 58.4 V, corresponding to approximately 4.17 V per cell, with a moderate safety buffer rather than aggressive full charging.
Environmental specifications: operating temperature -20°C ~ 55°C; derating occurs above 45°C. Relative humidity ≤95%, altitude ≤2000 m, IP21 protection rating. IP21 protects against finger contact and vertical dripping water, but not heavy rain or immersion. It cannot be placed in open exposure; shelter under eaves or within an enclosure is mandatory.
Lithium iron phosphate cells, cycle life ≥8000 cycles under specified conditions: 90% DOD, 25°C, 0.5C rate. These conditions matter more than the cycle figure itself. The same battery will degrade far faster when operated at 45°C with frequent full charge-discharge cycles than under 25°C shallow cycling.
Up to 15 units can be paralleled for a maximum capacity of 240 kWh. This leaves room for future expansion: once two more freezers or an extra air conditioner are added in a couple of years, the battery bank can be upgraded by paralleling another unit without replacing existing hardware.
The local display shows voltage, current, state of charge and temperature, so operational status can be checked without a computer connection.
03 PV string configuration specification
This section requires precise calculation and is often vaguely described.
Five modules per string. Under STC, open-circuit voltage per string: 51.4 V × 5 = 257 V. Operating voltage per string: 42.59 V × 5 = 212.95 V. The inverter MPPT window spans 150 V to 425 V. At first glance, 257 V sits within the acceptable range.
Yet field conditions in Ghana differ greatly from laboratory settings. When mounted on the roof, module rear surface temperature runs 25–30°C above ambient, reaching 65–70°C at noon. With an open-circuit voltage temperature coefficient of roughly -0.29%/°C, a 45°C temperature rise drops the string open-circuit voltage to about 223 V. Operating voltage falls even more sharply, around -0.35%/°C, bringing it down to approximately 179 V.
For ten modules, the optimal arrangement is two strings of five modules each.
Wiring scheme: String 1 connects to MPPT Channel 1;
String 2 connects to MPPT Channel 2.
Ten modules are fully utilised across the two independent channels.
Three key advantages of this configuration:
- Dual independent MPPT tracking. Partial shading or temperature deviation affecting one string will not disrupt the other.
- Matched string voltage balances loading across the two channels, simplifying troubleshooting and data logging.
- Adequate current margin with separate cabling for each string improves DC circuit reliability.
Note: Each MPPT channel is capable of supporting two strings, yet we do not utilise the full capacity here. For ten modules, stable operational voltage takes priority over filling every available port. Two strings of five represent the balanced outcome of port rating, voltage range, current limits and site construction constraints.
04 Operation from sunrise to sunset
System Operation Principle Video
6:00 a.m.: Dawn breaks. PV output remains negligible. The inverter stands by, with battery state of charge at 20%–25%, leftover from the previous night.
6:30 a.m.: String voltage crosses the 125 V startup threshold. The inverter wakes. It prioritises powering the well pump before charging the battery. Soft morning irradiance suits this non-urgent load. Water fills the basin, and daily routines begin.
9:00 a.m. – 10:00 a.m.: Solar power climbs to 2–4 kW. The refrigerators, which accumulated heat overnight, run their compressors continuously. Power feeds the loads first, with surplus going into the battery. SOC rises from 25%, charging current ranging 60–90 A, visible on the battery touchscreen.
11:00 a.m. – 2:00 p.m.: Peak irradiance window at roughly 5 kW. The battery usually charges above 80%. Excess energy runs the washing machine, induction cooker and charges portable devices. People stay indoors out of the sun while the array harvests power overhead.
2:00 p.m. onwards: Clouds roll in. Output drops to 2 kW, 1 kW or lower. The battery bridges the gap. Refrigerators and fans keep running without perceptible interruption. This seamless transition is the true value of the system.
5:30 p.m.: Sunset. Battery SOC reaches 90% or higher.
6:00 p.m.: Lights switch on, the induction cooker starts and the air conditioner engages. This is the most demanding window: instantaneous load of 5–6 kW drawn from the battery at around 100 A, well below the 200 A discharge limit. The inverter’s 2× surge rating is never fully stressed.
11:00 p.m.: Lights are turned off one by one. Only air conditioning, refrigerators and fans remain active, drawing 1.2–1.6 kW. Battery SOC gradually falls from 70%, settling at roughly 20% by sunrise.
What about rainy days? Ghana’s rainy season brings unpredictable prolonged cloud cover. Two consecutive overcast days may limit PV output to a few hundred watts. The battery can support one full night but not a second. Mains supply supplements power when available; if mains fails, the diesel engine takes over again. It is not removed, nor does it need to be. A well-designed off-grid hybrid system does not eliminate diesel entirely — it reduces it from a daily necessity to a rarely used backup, refuelled only once every few weeks.

Key PV Equipment Indoor Installation Diagram
05 After 11 p.m.
Past 11 p.m., the courtyard lights go out one after another. Only the small green indicator light on the freezer glows steadily in the dark.
The diesel engine stays quiet. It has not run for days, and the oil level in the drum drops at an extremely slow pace.
This system does not transform the courtyard into something sophisticated. The panels, battery cabinet and inverter have no fancy interface. It simply makes evening life predictable: fish stay frozen safely overnight, children can study under steady lighting, and extra fans can be switched on for guests without anxious load calculations.
In many such courtyards across Ghana, electricity is less about cost and more about availability and stability. Ten solar panels, an 8 kW inverter and a 16 kWh battery cannot achieve extraordinary things. Yet they are enough for this combined shop and home to turn those difficult evening hours into just another ordinary day.