Product Category

29.9/30/36/40/50 kW Grid-Tied Inverters

29.9–50 kW three-phase commercial and industrial hybrid grid-tied inverter with multi-channel MPPT tracking; supports UPS black start and parallel off-grid operation; no derating at high temperatures; compatible with weak power grids; high overload capacity; core unit for factory photovoltaic energy storage systems.
CONTACT US

Product Details

Datasheet SW 29.9K-XHU SW 30K-XHU SW 36K-XHU SW 40K-XHU SW 50K-XHU
Input Data(PV)
Max.recommended PV power
(for module STC)
59.8kW 60kW 72kW 80kW 100kW
Start voltage 195V
Max.DC voltage 1100V
Nominal voltage 620V
Max.open circuit voltage of PV 1000V
Operating voltage range 180V-1000V
Full load DC voltage range 375V-850V 375V-850V 450V-850V 500V-850V 620V-850V
Max.input current per MPP tracker 40A
Max.short-circuit current per MPP tracker 50A
No.of PV strings per MPP tracker
No.of MPP trackers
Battery Data(DC)
Battery voltage range 200-900V
Full load battery voltage range 200-800V 200-800V 225-800V 250-800V 310-800V
Recommended battery voltage 512V
No.of battery input
Max.charging/discharging current 55A*3
BMS communication RS485/CAN
Input/Output AC
AC input/output nominal power(Grid) 59.8kW/29.9kW 60kW/30kW 72kW/36kW 80kW/40kW 100kW/50kW
oparen powercna 59.8kVA/29.9kVA 66kVA/33kVA 79.2kVA/39.6kVA 88kVA/44kVA 110kVA/55kVA
Max.input/output current(Grid) 90.6A/45.3A 100A/50A 120A/60A 133.3A/66.7A 166.7A/83.3A
Max.input current(GEN/AC couple) 90.6A/45.3A 100A/45.5A 120A/54.5A 133.3A/60.7A 166.7A/75.7A
Aepassthirugh curent 200A
Nominal AC voltage/range¹ 380/400V-15%~10%
Nominal AC grid frequency/range 50Hz/60Hz,45-55Hz/55-65Hz
Power factor(@nominal power) >0.99
Adjustable power factor -1..+1
THDi <3%
AC grid connection type 3P3W+PE/3P4W+PE
Backup Power
AC nominal output power 29.9kW 30kW 36kW 40kW 50kW
Max.AC apparent power 29.9kVA 45kVA 54kVA 60kVA 75kVA
Nominal AC voltage 220V/230V(L-N),380V/400V(L-L)
Nominal AC frequency 50/60Hz
Max.output current 68.0A 68.2A 81.8A 91A 113.6A
Overload capability 1.5 times of rated power,10s
THDv <3%(@Linear full load)
Switch time ≤10ms
Efficiency
Max.efficiency 98.1%
Protection Devices
DC reverse polarity protection Yes
Battery reverse protection Yes
Insulation resistance monitoring Yes
AC/DC surge protection Type ll
AC short-circuit protection Yes
Ground fault monitoring Yes
Grid monitoring Yes
String monitoring Yes
Anti-islanding protection Yes
Residual-current monitoring unit Yes
General Data
Dimensions(W/H/D) 920/585/320mm
Weight 90kg
Operating temperature range -30℃-60℃(>50℃ derating)
Noise emission ≤55dB
Altitude 4000m
Topology Transformerless
Cooling Smart air cooling
Protection degree IP66
Relative humidity 0~95%
Interfaces
Display OLED+LED/APP
Interfaces RS485/USB/CAN,WIFI/LAN(Opt)
Warranty:5/10 years Yes/Opt
CE/CB,ROHS,IEC62109-1,IEC62109-2,IEC 62477-1,EN 62920,IEC 61000-6-4,IEC61000-6-2,IEC 61000-3-12,
IEC 61000-3-11,EN 55011,IEC 62116,IEC 61727,IEC 61683,IEC 60068-2-1,NRS097-2-1